|

TRACTOR DRIVEN ALTERNATOR
OWNERS INSTRUCTION MANUAL
EXTREME CAUTION: Please be advised that
failure to anchor the PTO Driven Alternator may cause the unit to flip and inflict severe
injury and/or damage to the operator and/or surrounding structure and equipment. It
is highly recommended that the alternator be bolted down and securely anchored to a
concrete slab that has been well reinforced with steel re-bar. Friesen Electric Inc.
will not be liable for any injury or damage incurred as a result of negligence regarding
installation. Follow the instructions in the owner's manual specifically when
putting this alternator into service. |
IMPORTANT: All standby power plants
including Tractor Driven Alternators should be periodically exercised. For proper
maintenance of your Tractor Driven Alternator, it should be operated for one hour carrying
rated load at least twice a year. This will assure that your alternator is in
operating condition and ready for use when an emergency condition develops. |
TRACTOR
DRIVEN ALTERNATORS
TABLE
OF CONTENTS
- Introduction
- Operating the Alternator
- Maintenance Requirements
- What is a
Static Excited Type Generator?
- PTO Alignment
- Operation of
Tractor Driven Alternators
- Procedure for Use
- Service Diagnosis
- Testing of Rectifier
Assembly
- Handling
Procedure for Rectifiers
- Sticky Brushes
- Build Up of the
Excitation Field
- Field
Check of Armatures
- Testing
a Field Circuit
- Lubricant
Cross Reference Chart
INTRODUCTION:
The
words generator & alternator are used interchangeably but have the same meaning.
This manual covers standby generators driven by the power take-off of a farm
tractor. These generators use a static excitation system which will be discussed in later
paragraphs of this manual. All generators are carefully inspected, tested, and packaged
for shipment at the factory. The generator should be unpacked as early as possible upon
receipt and inspected for damage which may have occurred during shipment. Any damage noted
should be promptly reported to the carrier in order that a claim can be filed to recover
the cost of the damage. If at all possible, this damage should be noted on the freight
bill at the time of delivery. If the damage appears to be of a major nature, the generator
should not be operated until the fault has been corrected.
Tractor
driven generators are designed to deliver voltage and current similar to that of the
normal power line. Equipment that can be operated on normal power can also be operated by
the generator, provided that the capacity of the generator is not exceeded. It should be
remembered that the power line, for all practical purposes, is backed by an unlimited
generator.
When not
in use the generator should be stored in a clean dry location. All types of mechanical
equipment suffer from long periods of storage without use. The generator should be used at
frequent intervals at some convenient time. By this procedure deterioration will be
prevented and any possible fault will be noted before any emergency condition develops.
OPERATING THE ALTERNATOR
A double
throw manual transfer switch must be used with a standby generator. The load, connected to
the normal terminals of the transfer switch, is energized by the normal power line when
the switch is in the normal position. The generator, connected to the emergency terminals
of the switch, furnishes power when the switch is in the emergency mode position. When the
normal power fails, the generator is attached to the tractor by means of the power
take-off shaft.
Start
the tractor and adjust the speed until the pointer of the voltmeter on the generator panel
registers on the high side of the green portion of the colour band.
Check
the connected load to assure that all heavy electrical equipment is disconnected.
Move the transfer switch
handle to the emergency position connecting the load to the generator.
Switch
on all required electrical equipment within rated capacity of the generator maintaining
tractor speed to cause the voltmeter to remain in the green portion of the colour band.
If the
circuit breaker of the generator control panel trips during operation, the connected load
is greater than the rated generator capacity.
Reduce
the load by disconnecting any non-essential equipment during emergency conditions.
After a
short delay, indicating that the power restoration is not temporary, the transfer switch
can be returned to the normal position and the tractor drive generator shut down.
After
the load has been returned to normal power, normal precautionary measures should be made
for protection of the tractor drive generator. If the generator is mounted on an
off-highway trailer, such as the Winpower TD-M/73, it should be stored in a barn or
machine shed in a dry and clean location. The generator should be covered with a tarpaulin
to prevent the entrance of dust, chaff, and/or moisture. Generators installed in a
permanent location should be mounted on a concrete base of at least 3" reinforced
slab. Some provision should be made for a water and dust-tight cover to remain in place
during stand-by conditions. A simple frame enclosure including doors for connecting to the
power take-off and for ventilation is a very worthwhile provision. A typical weather
protected installation is shown in Figure 1.
MAINTENANCE REQUIREMENTS
Maintain
proper oil level in the PTO gear case. See the list attached for lubricants. Do not
overfill, maintain level to the small pipe plug approximately 4" from the bottom of
the gear case on the gear case cover.
Make
frequent inspection of the collector ring brushes. Brushes should move freely in the brush
holders. When lifted from the surface of the collector ring by the brush shunt, and
released, the brush should snap back in contact with the collector ring. Inspect
brushes for wear. A brush that does not fill at least two thirds of the brushholder should
be replaced.
Inspect
for loose or broken wiring connections. Make sure that wiring connections are not loosened
at the brushholder.
Do not
allow dirt or chaff to collect in the interior of the generator or the ventilation
openings. Inspect for indication of the entrance of mice into the generator. The inlet and
outlet openings are louvered, but possible damage to the louvers could occur. Mice
can destroy the generator winding.

WHAT IS
A STATIC EXCITED TYPE GENERATOR?
The word
"static" means without motion; thus, the term "static excited" means
that the excitation current for the field is supplied without the use of outmoded rotation
type of excitation. Commutators and commutator brushes with the inherent problems of
commutation and maintenance are not used.
In the
FRIESEN static excited alternator, the alternating current output of the generator is
rectified by means of a full-wave silicon diode bridge. Resulting direct current is used
to supply the stationary field coils.
There is
also a circuit in the alternator excitation system to maintain a relatively constant
voltage as the load is varied.
The
excitation circuit uses only one rectifier bridge. In this system the divided primary of
the current transformer is connected in series with load lines. The secondary output of
this transformer is then connected to the shunt field and is also controlled by a reactor
in series with one connection to the AC side of the bridge. The reactor serves to control
the energy at no load, which reduces as load is added and also maintains stable voltage
output by varying the field strength.
The use
of the current transformer provides not only a means for variation of field strength for
normal loading, but also a means for "forcing the field" during sudden momentary
overloads such as are encountered in the starting of motors. This means the intermittent
capacity of the alternator can be increased to the higher rating indicated in the model
designation.
PTO ALIGNMENT
Position
the alternator in such a manner that the power takeoff shaft is as near to direct line in
all directions as possible. This will increase the life of the power takeoff shaft, reduce
ware on bearings of both the power takeoff and the alternator, and reduce vibration. The
maximum angle from a straight line should not exceed 10°. For the nominal power takeoff
shaft length of 42", 10° is equal to 8" misalignment. For extended distance the
maximum misalignment would increase 2" for each foot. For Example: For a 6' PTO shaft
the maximum misalignment is 12" from a straight line.
OPERATION OF TRACTOR DRIVEN
ALTERNATORS
When the
alternator is not in use it must be maintained in a clean and dry condition. The inside of
the panel, frame, and air inlet and outlet must be free from dirt and chaff.
When connection is made
at the meter pole, a double throw manual transfer switch must be used. Normal power is
connected to the top, the load at the centre, and the alternator at the bottom of the
switch. Warranty is void if a transfer switch is not used.
PROCEDURE FOR USE
Set
the main circuit breaker on the alternator panel to "off."
Connect
the power take-off shaft securely to the alternator and the tractor. Position as near to a
straight line as possible.
Adjust
power take-off speed to maximum then back down to maintain the voltage indicator in the
green portion of the colour band.
Place
plug in receptacle. Place transfer switch in the emergency position.
Place
the load circuit breaker in the "on" position. If the breaker trips, check for
short circuit or grounded connection in the load cable to the double throw switch. A
breaker that trips from overload or short circuit must be reset by moving to
"off" before re-closing.
Keep
meter in the green by adjusting tractor speed.
The
return of normal power will be indicated by the lamp on the front of transfer switch;
applicable only when the transfer switch is equipped with indicating lamps. After
sufficient time to assure that power restoration is not temporary, return the transfer
switch to normal power.
Place
the alternator circuit breaker in "off" position. Do not remove plug before
opening the breaker.
Slowly
reduce power take-off speed to a minimum and disengage the power take-off. Some
tractors have a brake on the power take-off which stops the shaft instantly. Stopping
the alternator rotor instantly from rated speed may result in a broken shaft.
- Exercise PTO
alternator for one hour carrying rated load at least twice a year.
SERVICE DIAGNOSIS
This
section contains information on how to trouble shoot for low output voltage, high output voltage, excessive heating, no output voltage, defective armatures, unsteady voltages, and slow voltage buildup.
LOW OUTPUT VOLTAGE
Possible Cause |
Remedy |
| Low speed
|
Check for overload on the
engine or tractor. Defective
governor. Check governor spring tensions, tight or defective throttle levers and
joints.
Defective engine (see engine check list). |
| High line loss.
Indicated by lower voltage at load than at generator terminals |
Increase size of line
wiring. Might also be the result of loose connection which will be indicated by
excessive heating at the loose connections. |
| Shorted or grounded field
coil. In some cases one coil only, that is shorted or grounded, will reduce voltage
to approximately one half of rating. |
See information for testing
field circuits. |
HIGH OUTPUT VOLTAGE
Possible Cause |
Remedy |
| Excessive speed. |
Check governor linkage, spring
tensions, etc. Governor linkage must be free from dirt and gum. |
EXCESSIVE HEATING
Possible Cause |
Remedy |
| Clogged ventilating inlet
and/or outlet. |
Clean screens, make sure
interior of generator is unobstructed. |
NO OUTPUT VOLTAGE
Possible Cause |
Remedy |
| Poor brush contact:
Brushes tight in holder. |
Clean brush holder.
Brush should move freely in holder. |
| Weak brush spring tension. |
Brush spring tension should
snap brush into contact with ring when lifted and released. |
| Film on collector rings caused
by corrosive or dirty atmosphere. |
Clean rings with fine
sandpaper during rotation of armature. Caution: Tape sandpaper
to stiff cardboard for safety. |
| Defective rectifier bridge
(see method of checking
bridge) |
Replace defective bridge
assembly. |
| Open field circuit (see
illustration for method for checking, Figure
2) |
Replace open coil(s) or repair
if open connection is in the connecting loads. |
| Grounded or shorted field
coil(s). |
Replace grounded coil(s) and
insulation or repair damage. |
| Loss of residual
magnetism. This is a condition brought about by some unusual condition. It
will usually occur after disassembly of the field frame. |
Restore magnetism. |
DEFECTIVE ARMATURE
Possible Cause |
Remedy |
| Shorted winding. This
can be identified by the use of a "growler" at a competent rewinding shop. |
Replace the armature.
(Include generator model and serial number on the order). |
| Grounded armature. Check
winding by test lamp or high potential tester from collector rings to shaft. |
Replace the armature.
(Include generator model and serial number on the order). |
| Open armature circuit.
Measure circuit between rings with an ohmmeter. Should have a circuit between any
pair of rings |
Replace the armature.
(Include generator model and serial number on the order). |
VOLTAGE UNSTEADY
Possible Cause |
Remedy |
| Loose connection, probably at
rectifier. |
Tighten with pliers. |
SLOW VOLTAGE BUILDUP
Possible Cause |
Remedy |
| Slow voltage buildup, or no
voltage buildup, unless load is applied. |
See below. |
| Excessive air gap between
armature and field poles. |
Shim all poles est. 0.007. |
| Not enough air gap in choke.
|
Remove top part of choke and
install thickness of a regular piece of paper until voltage builds up in 3 to 5 seconds or
260V no load on 120/240V unit. Replace top of choke and tighten the bolt.
Loose bolts will cause chatter and unstable voltage. |
TESTING OF
RECTIFIER ASSEMBLY
Remove
the lead from the positive ( + ) terminal and one of the leads going to AC terminal of the
bridge.
Connect
black lead of meter to positive ( + ) terminal of bridge and red lead to one of the AC
terminals of bridge. Meter should read about 20 Ohm.
Now,
reverse the lead on bridge terminals. Meter should read open circuit or infinite
resistance.
Connect
black lead of meter to ( + ) terminal and red lead to other AC terminal of bridge. Meter
should read about 20 Ohm.
Now
reverse the leads on bridge terminals. Meter should read open circuit or infinite
resistance.
Connect
red lead of meter to ( - ) terminal of bridge and black lead to one of the AC terminals of
the bridge. Meter should read about 20 Ohm.
Reverse
the leads and you should read infinite resistance.
Connect
red lead of meter to ( - ) terminal of the bridge and black lead of meter to other AC
terminal of the bridge. Meter should read about 20 Ohm.
Now
reverse the leads and you should observe infinite reading on your meter.
All
eight steps are described for a good bridge.
A
shorted diode will give zero resistance reading in both directions.
A low
resistance reading of 2 Ohms or so will show leakage current and diode should be replaced.
An open
diode will give a high resistance (infinite) reading in both directions.
HANDLING PROCEDURE FOR RECTIFIERS (Diodes & Bridge
Assemblies)
Rectifiers
should be handled in a manner which avoids the possibility of sudden shocks being applied,
such as those encountered in dropping from a work bench to a hard floor. Damage done to
the rectifier by such shocks may not be detected by subsequent testing, yet may cause poor
system reliability.
Any
lead trimming or forming operations should be done with care to avoid damaging the leads
or the glass header seals.
Leads
should never be bent or twisted. If lead forming is necessary the lead should be supported
so that no bending occurs closer than 1/8 inch to the rectifier body, and that header
seals are not fractured or broken. If this seal is broken, it removes mechanical support
for the lead and allows entry of moisture into the rectifier, almost assuring early
failure.
Care
must be taken during all soldering operations. It is unsafe to exceed the general
specification to which diodes are tested for solder ability. This is 10 ±2 seconds at a
temperature of 230°C +5°C at a point 1/16" ±1/32" from the diode body. This
is not as restrictive as it may sound, since 230°C is 446°F and 60/40 solder melts at
375°F, and with proper procedure & soldering tools a solder joint can be made in 4 to
7 sec. Also, solder joints are almost never made this close to the diode body. Heat sinks,
such as a pair of needle nose pliers or alligator clips, can be attached to the lead
between the solder joint and the diode body to further reduce the possibility of heat
damage.
Also,
precautions should be taken to prevent solder or flux bridging which causes a conductive
path across the case of the rectifiers. As a precaution all flux should be removed by
using alcohol and a small brush. Pay particular attention to assure that glass header
seals are free of all flux.
STICKY BRUSHES
Brushes
must move freely in the brushholders to maintain contact to the slop rings. The field
circuit begins at the brushholders. If the brush does not maintain contact to the ring, or
if a film has developed on the ring from lack of use and maintenance, there will be no
current in the field coils; consequently, the field strength will not increase from the
low residual value resulting in lack of voltage buildup. The cause in both cases is
usually lack of maintenance and improper storage.
BUILD UP OF THE
EXCITATION FIELD
Occasionally
an alternator will seem to be defective as there is no indication on the voltmeter on
start up. This will sometimes be caused by a too careful increase in power take-off speed.
Rated speed is not actually reached. The better procedure is to adjust to maximum, then
back down to maintain the indication in the "green" portion of the colour band.
When repairs have been
made or the alternator has not been used for a long period it may be necessary to
"flash the field." An inexpensive tool using a small step-down transformer is
the best means for this purpose. It has a nominal input of 125V, 25VV secondary and 2
ampere rating. Avoid the use of a variable transformer. Reversal of power line and
alternator ground may cause damage.
With the
alternator operating, plug the transformer into a wall outlet and insert the prods into
the 125V outlet on the alternator panel. Remove at once when an indication is shown on the
voltmeter.
FIELD
CHECK OF ARMATURES (Tractor Drives)
Instrument
required -- Volt-Ohm Meter. Set on Ohm X1 scale.
Check
Ohm Meter by touching leads together. Reading should be zero.
Lift
all brushes form armature that is to be checked.
First
check to find out if armature windings are grounded (most probable).
a.
Connect one lead of Ohm Meter to ground.
b.
Touch other lead to each ring. Meter should stay at infinite (not move).
c. If
reading is indicated, armature is grounded and should be replaced.
d. If
armature has commutator, it should not indicate ground.
Second
check to find out if armature windings are open.
Symptom:
when generator was running no voltage on one line to neutral, or on 115V unit no voltage.
Lift all brushes.
a.
Armature 3 Rings, 1Ø or 3Ø, 3 Wire
Connect
one ohm meter lead to Ring 1. Touch other lead to Ring 2. Meter should read
Zero or very low. Then touch lead to Ring 3. Meter should read Zero. Winding
is open if reading is infinite.
b.
Armature 4 Rings, 3Ø, 4 Wire
Connect
one ohm meter lead to Ring 1 Touch other lead to Ring 2 Reading should be near zero
Touch other lead to Ring 3 Reading should be near zero Touch other lead to
Ring 4 Reading should be near zero
c.
Armature 4 Rings, 1Ø
This
armature has two windings One starting on Ring 1 ending on Ring 2, and one starting
on Ring 3 ending on Ring 4.
Connect
ohmmeter one lead to Ring 1. Other lead to Ring 2, meter should read near zero.
Other lead to Ring 3, meter should read infinite. Other lead to Ring 4, meter
should read infinite. Connect one lead to Ring 3. Other lead to Ring 4, meter
should read near zero. Other lead to Ring 1, meter should read infinite. Other
lead to Ring 2, meter should read infinite
FIGURE 2

NOTE:
Fields alternate "straight" and "crossed" to provide proper polarity.
When ordering replacement coils be sure to include Model, Type, and Serial Number.
TESTING A FIELD CIRCUIT Disconnect field
leads F1 and F2
Measure
resistance of entire field circuit as shown in Figure 2. A resistance of less
than the range shown on the table indicates a shorted coil. The defective coil can be
identified by measuring the resistance of the individual coils. A coil with an appreciable
lower resistance has shorted turns.
A
reading of no deflection or very little deflection of the meter pointer indicates a
defective coil or broken interconnection. Inspect all interconnecting wires for tight and
un-corroded connection. Each coil should measure approximately ¼ of the total specified
resistance. A very high resistance indicates broken internal wires.
A
grounded field can be identified by connecting one ohmmeter lead to one field lead and
touching the other to an unpainted spot on the field ring. Make sure that none of the coil
leads are in contact with the ring. A grounded field can usually be corrected by repairing
the insulation once the grounded point or points are located.
NOTE:
Whenever the field could have been removed and/or replaced, the field must be
re-energized.
LUBRICANT CROSS REFERENCE CHART (For
Chain Driven Units)
| Manufacturer |
Description |
| Alemite |
HD Gear Oil No. 3 |
| Allube (Far-Best
Corp.) |
Moly-Shield IGO 80 |
| America Lubricants
Co. (Alubco) |
Albuco Moly Ultra-Tec Lube, SAE 80 |
| Amoco Oil Co.
(Standard Oil Co. of Indiana) |
Amogear EP1 |
| Ashland Oil &
Ref. Co. |
EP Compound No. 30 |
| Atlantic-Richfield
Co. |
Pennant NL S-315 |
| Bel-Ray Co., Inc. |
Bel-Ray 100 Gear
Oil #50 |
| Boron Oil Co. |
Gearep 80 |
| Brooks Oil Co. |
Brooks L-40 |
| Cato Oil and
Grease Co., Inc. |
Universal 2105
Gear Lub 80 |
| Champlin Petroleum
Co. |
MGX #3 |
| Chevron Oil Co.
(Standard Oil Co. of California |
Chevron NL Gear
Compound 68 |
| Cities Service Oil
Co. |
Citgo EP Compound
55 |
| Continental Oil
Co. |
Milgear L50 |
| DuBois Chemicals |
MPO-30 |
| Exxon Co., U.S.A. |
Spartan EP68 |
| Fiske Refining
Company |
APG 80 |
| Georgia-Carolina
Co. |
G-C Yukol E.P. #80 |
| Gulf Oil Corp. |
E.P. Lubricant 55 |
| Imperial Oil &
Grease Co. |
Molub-Alloy 804 |
| Kendall Refining
Co. |
Kendall NS-MP SAE
80 W |
| Mobil Oil Co. |
Mobilgear 626 |
| National Refining
Co. |
EP Compound No. 30 |
| Parr Inc. |
1022 |
| Pennwalt Corp.
(Keystone Div.) |
WG 5X |
| Pennzoil Co. |
Maxol EP #1 or
MP4080 |
| Phillips Petroleum
Co. |
Philube ILB Gear
Oil EP-3 |
| Shell Oil Co. |
OMALA 33 |
| Standard Oil Co.
(Ohio) |
Gearep 80 |
| Stewart-Warner
Corp. |
HD Gear Oil No. 3 |
| Sun Oil Co. |
Sunep 1050 |
| Texaco |
Meropa 68 |
| Tower Oil &
Technology Co. |
Express Gear Lube
EF |
| Valvoline Oil
Company |
EP compound No. 30 |
| While & Bagley
Co. |
Oilzum Super Gear
Oil SAE 80 EP |
| Union Oil Co. of
California Western Region |
Union PB Gear Lube
50 |
| Union Oil Co. of
California Eastern Region |
Union Ext. Duty NL
50 |
| United Refining
Co. |
Emblem APG Lube
ZEP (80) |
| West Penn Oil Co.,
Inc. |
W/P Hi-Gear
Compound No. 1 |
Return to Friesen Electric Home
Page
Find out how to Contact Us
©1998, Friesen Electric Inc.
Serving you since 1950
|